DocumentCode :
3609388
Title :
Experimental studies of influence of different electrodes on bridging in contaminated transformer oil
Author :
Mahmud, S. ; Chen, G. ; Golosnoy, I.O. ; Wilson, G. ; Jarman, P.
Author_Institution :
Sch. of Electron. & Comput. Sci., Univ. of Southampton, Southampton, UK
Volume :
22
Issue :
5
fYear :
2015
fDate :
10/1/2015 12:00:00 AM
Firstpage :
2433
Lastpage :
2441
Abstract :
Contaminated transformer oil has been tested under non uniform electric fields and the effect of different electrode systems presented in this paper. Three different electric fields were examined i.e. DC, AC and DC biased AC. These experiments revealed that with all the different electrodes arrangements, contaminated particles always formed bridges between electrodes under DC electric field. The bridges were thicker and more particles were attracted with more uniform electric field (spherical electrode) than with a divergent electric field (needle-plane).
Keywords :
electric fields; electrodes; transformer oil; DC electric field; bridge formation; contaminated transformer oil; divergent electric field; electrode system; needle-plane electric field; nonuniform electric field; spherical electrode; Bridge circuits; Electric fields; Electrodes; Force; Needles; Oil insulation; Power transformers; Dielectrophoresis; HVDC transformer; bridging.; contamination; dragforce; failure;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2015.004846
Filename :
7311015
Link To Document :
بازگشت