DocumentCode
3609388
Title
Experimental studies of influence of different electrodes on bridging in contaminated transformer oil
Author
Mahmud, S. ; Chen, G. ; Golosnoy, I.O. ; Wilson, G. ; Jarman, P.
Author_Institution
Sch. of Electron. & Comput. Sci., Univ. of Southampton, Southampton, UK
Volume
22
Issue
5
fYear
2015
fDate
10/1/2015 12:00:00 AM
Firstpage
2433
Lastpage
2441
Abstract
Contaminated transformer oil has been tested under non uniform electric fields and the effect of different electrode systems presented in this paper. Three different electric fields were examined i.e. DC, AC and DC biased AC. These experiments revealed that with all the different electrodes arrangements, contaminated particles always formed bridges between electrodes under DC electric field. The bridges were thicker and more particles were attracted with more uniform electric field (spherical electrode) than with a divergent electric field (needle-plane).
Keywords
electric fields; electrodes; transformer oil; DC electric field; bridge formation; contaminated transformer oil; divergent electric field; electrode system; needle-plane electric field; nonuniform electric field; spherical electrode; Bridge circuits; Electric fields; Electrodes; Force; Needles; Oil insulation; Power transformers; Dielectrophoresis; HVDC transformer; bridging.; contamination; dragforce; failure;