DocumentCode :
3611658
Title :
Impact of GICs on Power Transformers: Overheating is not the real issue.
Author :
Girgis, Ramsis S. ; Vedante, Kiran B.
Author_Institution :
ABB Power Transformer Plant, St. Louis, MO, USA
Volume :
3
Issue :
4
fYear :
2015
Firstpage :
8
Lastpage :
12
Abstract :
There has been some misconception in the electric power industry that geomagnetically induced currents (GICs) can cause significant overheating damage to the majority of medium and large power transformers. Because of the nature of GICs, the majority of power transformers would not experience damaging overheating because of them. This article presents the real issue with GICs, which is that the combination of the increase of reactive power absorption and injected current harmonics into the power system could result in compromised grid stability.
Keywords :
power system harmonics; power transformers; reactive power; GIC; electric power industry; geomagnetically induced currents; grid stability; overheating damage; power system; power transformers; reactive power absorption; Current measurement; Geomagnetism; Harmonic analysis; Power system stability; Power transformers; Reactive power; Transformers;
fLanguage :
English
Journal_Title :
Electrification Magazine, IEEE
Publisher :
ieee
ISSN :
2325-5897
Type :
jour
DOI :
10.1109/MELE.2015.2480355
Filename :
7343042
Link To Document :
بازگشت