DocumentCode :
3612719
Title :
Partial discharge measurement and analysis at standard oscillating switching and lightning impulses on a GIS with artificial protrusion defects
Author :
Ming Ren ; Chongxing Zhang ; Ming Dong ; Rixin Ye ; Aici Qiu
Author_Institution :
State Key Lab. of Electr. Insulation for Power Equip., Xi´an Jiaotong Univ., Xi´an, China
Volume :
22
Issue :
6
fYear :
2015
fDate :
12/1/2015 12:00:00 AM
Firstpage :
3459
Lastpage :
3469
Abstract :
Partial discharges (PDs) induced by artificial fixed protrusions inside an SF6 gasinsulated switchgear (GIS) test object under oscillating switching and lightning impulse voltages (OIVs) were investigated experimentally. The features of PD current and light pulses (sequences) under impulses were analyzed. The characteristics of PD behaviors under oscillating lightning impulse (OLI), oscillating switching impulse (OSI) and 50 Hz AC voltages were studied according to their statistical distributions. The experimental data were quantitatively analyzed to compare the effectiveness of AC and OIV voltages in exciting the PDs in terms of PD inception and PD activity. Most PDs occurred successively around the peaks of the oscillation period of OIVs and periodical PD sequences were formed. Compared to positive point PDs, negatives occurred more frequently, but with smaller magnitudes. The positive OSI was found to have relative high efficiency in exciting PDs from fixed protrusion comparing to other types of voltage investigated. The occurrence frequency of PD under negative OLI was one or more orders of magnitude greater than that under AC voltage. The average PD magnitudes under positive OIVs were much greater than the others. Both the average PD magnitude and the occurrence frequency were greater at 0.2 MPa, than at 0.4 MPa. This indicates that the AC PD test is not very sensitive to local enhanced field defects, such as fixed protrusions on conductors, because of the limited PD measurement sensitivity and the corona stabilization under AC voltage.
Keywords :
SF6 insulation; corona; gas insulated switchgear; lightning; partial discharge measurement; statistical distributions; GIS; OIV; OLI; OSI; SF6 gas insulated switchgear; artificial protrusion defect; corona stabilization; oscillating lightning impulse; oscillating switching and lightning impulse voltages; oscillating switching impulse; partial discharge measurement; periodical PD sequence; statistical distribution; Gas insulation; Open systems; Partial discharge measurement; Partial discharges; Standards; Switches; Voltage measurement; GIS; Oscillating impulse; SF6; gas insulated switchgear; partial discharge;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2015.005207
Filename :
7367543
Link To Document :