Abstract :
According to the IEC Standard, the insulation performances of power apparatus under lightning impulse voltages are evaluated by the withstand test of standard lightning impulse voltage, with the wave front/tail time of 1.2/50 μs. However, the standard lightning impulse voltage originally obtained from the transmission lines or triggering lightning towers, is quite different from the invading lightning impulse voltage in the power transformers. Hence, in this work, an attempt has been made to obtain the waveform characteristics of invading lightning impulses in power transformers using an overvoltage online monitoring system. Energy Method was then proposed to convert the recorded oscillatory waveform into double-exponential waveform defined by IEC Standard. And the statistical waveform parameters of recorded invading lightning impulses, namely, the non-standard lightning impulses, were determined based on the Energy Method. Current insulation assessment methods, for example, the V-t characteristics, are far from satisfactory to meet the demand of insulation design for the power apparatus, whereas the impulse breakdown voltage-number of voltage applications characteristics (V-N characteristics) could well evaluate the long term performance of insulation system. Therefore, we experimentally identified the V-N characteristics of oil paper insulation under impulse voltage with different waveforms, including non-standard lightning impulse voltage, and then mathematically analyzed the obtained data. At last, the influence of wave front/tail time on the V-N characteristics of oil paper insulation was experimentally studied. The test results indicate that the insulation performances of oil paper insulation under repeated nonstandard lightning impulse voltages and under standard switching impulse voltages were better than that under repeated standard lightning impulse voltages. And the capacity to withstand repeated voltage became increasingly stronger with the incre- se in wave front time or the decrease in wave tail time. The breakdown voltage, however, was only related to the wave front time of applied impulse voltage.
Keywords :
IEC standards; lightning protection; power apparatus; power transformers; transformer insulation; IEC Standard; breakdown voltage; double-exponential waveform; energy method; impulse breakdown voltage-number; insulation performances; lightning impulse voltages; lightning towers; nonstandard lightning impulses; oil paper insulation; oscillatory waveform; overvoltage online monitoring system; power apparatus; power transformers; transformer insulation; transmission lines; voltage-number characteristics; Breakdown voltage; Electric breakdown; Insulation; Lightning; Power transformer insulation; Standards; Oil paper insulation; V-N characteristics; non-standard lightning impulse voltage; waveform parameters;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2015.005000
Filename :
7367559
Link To Document :
بازگشت