    Analysis of the insulated power-grid transient behavior after faulted phase tripping

  • Author

    N. Berbic;A. Nuhanovic;V. Madzarevic

  • Author_Institution
    Fac. of Electr. Eng., Univ. of Tuzla, Bosnia-Herzegovina
  • Volume
    3
  • fYear
    2004
  • fDate
    6/26/1905 12:00:00 AM
  • Firstpage
    987
  • Abstract
    The common cases of a nonselective operation of the phase to ground fault protection in the insulated power grids, which utilize inductive sensors for a voltage unbalance indication, are explained by ferroresonant processes in voltage transformers of healthy drains. This paper deals with phase to ground faults simulations in a known grid, that provide information about possible nonselective phase to ground faults protection operation.