DocumentCode
3623241
Title
Effect of source reactance on power transfer limited by voltage instability in compensated transmission systems
Author
K.S. Attri;C.S. Rao
Author_Institution
Tech. Teachers´ Training Inst., Chandigarh, India
Volume
5
fYear
1993
fDate
6/15/1905 12:00:00 AM
Firstpage
322
Abstract
The effect of generator reactance on power transfer limits of EHV lines operating on the verge of voltage instability and having different series and shunt compensation schemes is investigated. Numerical results for maximum power transfer, critical angular separation and critical voltage are given with respect to five different compensation schemes considering different line length, power factors and degrees of series and shunt compensation.
Keywords
"Voltage","Reactive power","Power generation","Power transmission lines","Transmission line theory","Stability","Steady-state","Shunt (electrical)","Availability","Transformers"