Title :
Modelling of a voltage transformer for transients
Author :
P. Imris;M. Lehtonen
Author_Institution :
Power Systems and High Voltage Engineering Laboratory, Helsinki University of Technology, Espoo FIN-02015 HUT, Finland
fDate :
6/1/2005 12:00:00 AM
Abstract :
This paper presents the modelling of a 110 kV inductive voltage transformer for transients. The inductive voltage transformer ratio typically changes a lot for frequencies up to the 50th harmonic. To make a good model in this frequency range is the main task of this paper. A traditional lumped, linear model that includes capacitances gives satisfactory results. A new method of model capacitance estimation has been developed and is presented. The capacitance estimation is based on a real transformer measurement and recalculations. The model response was tested in EMTP/ATP and compared to the real transformer. This method can be used for simple and accurate modelling of inductive voltage transformers up to 10 kHz.
Keywords :
"Voltage transformers","Mathematical model","Circuit faults","Frequency measurement","Capacitance measurement","Impedance measurement","Inductance measurement","Power measurement","Electrical resistance measurement","Immune system"
Conference_Titel :
Power Tech, 2005 IEEE Russia
DOI :
10.1109/PTC.2005.4524404