DocumentCode :
3638319
Title :
Influence of mounting temperature probes on the excitation winding on its temperature field
Author :
Zlatko Hanić;Marinko Kovačić;Mario Vražić
Author_Institution :
Department of Electrical Machines and Automation at the Faculty of Electrical Engineering and Computing at the University of Zagreb, Croatia
fYear :
2010
Firstpage :
1
Lastpage :
6
Abstract :
Accurate and reliable information about the temperature of the synchronous generator excitation winding hot spot is necessary to determine the dynamic limit caused by excitation winding overheating in the PQ diagram. For good estimation of a position and the hot spot temperature it was decided to mount 19 temperature probes on one pole of the 6-pole, 400 kVA, 50 Hz synchronous generator. Due to a large number of the probes and because the probes should be glued with the metal epoxy it was assumed that mounting of the probes will disrupt the temperature field of the excitation winding. To get the answer to this question the excitation winding resistance was measured before and after mounting the probes, in a hot and a cold state. Temperature rise can be estimated if the resistance ratio in the hot and the cold state is known. The paper also addresses the analysis of the measurement accuracy.
Keywords :
"Temperature measurement","Windings","Probes","Electrical resistance measurement","Current measurement","Voltage measurement","Resistance"
Publisher :
ieee
Conference_Titel :
Electrical Machines (ICEM), 2010 XIX International Conference on
Print_ISBN :
978-1-4244-4174-7
Type :
conf
DOI :
10.1109/ICELMACH.2010.5608106
Filename :
5608106
Link To Document :
بازگشت