DocumentCode
3645374
Title
Non-iterative algorithm of analytical synchronization of two-end measurements for transmission line parameters estimation and fault location
Author
Pawelstrok Dawidowski;Jan Iżykowski;Ahmet Nayir
Author_Institution
Wroclaw University of Technology, Wyspianskiego 27, 50-370 Wroclaw, Poland
fYear
2011
Abstract
This paper presents a new setting free approach to synchronization of two-end current and voltage unsynchronized measurements. Authors propose new non-iterative algorithm processing three-phase currents and voltages measured under normal steady state load condition of overhead line. Using such synchronization line parameters can be estimated and then precise fault location can be performed. The presented algorithm has been tested with ATP-EMTP software by generating great number of simulations with various sets of line parameters proving its usefulness for overhead lines up to 200km length.
Keywords
"Synchronization","Transmission line measurements","Fault location","Power transmission lines","Accuracy","Voltage measurement","Current measurement"
Publisher
ieee
Conference_Titel
Electrical and Electronics Engineering (ELECO), 2011 7th International Conference on
Print_ISBN
978-1-4673-0160-2
Type
conf
Filename
6140271
Link To Document