• DocumentCode
    3656650
  • Title

    Impact of primary substation and HV faults on suburban MV network topology and total costs

  • Author

    Robert John Millar;Bruno Sousa;Matti Lehtonen;Atte Pihkala;Eero Saarijärvi

  • Author_Institution
    Department of Electrical Engineering and Automation, Aalto University, Espoo, Finland
  • fYear
    2015
  • fDate
    5/1/2015 12:00:00 AM
  • Firstpage
    301
  • Lastpage
    306
  • Abstract
    The availability of electricity is of paramount importance in urban distribution networks, and one planning consideration is the way medium voltage network is protected against faults in the feeding primary substation or high voltage network. One approach is to provide primary substations with full redundancy, and another is to ensure backup from adjacent primary substations. This paper details the methodology to implement this consideration in a distribution network planning algorithm that has been under development for several years at Aalto University. A case study on a 10 kV suburban network area is demonstrated, comparing the benefit of endowing a GIS primary substation with dual HV busbars rather than just a single busbar, versus forcing backup to be available from the adjacent primary substations.
  • Keywords
    "Substations","Planning","Maintenance engineering","Circuit faults","Switches","Interrupters","Network topology"
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering, Energy and Electrical Drives (POWERENG), 2015 IEEE 5th International Conference on
  • Print_ISBN
    978-1-4673-7203-9
  • Electronic_ISBN
    2155-5532
  • Type

    conf

  • DOI
    10.1109/PowerEng.2015.7266335
  • Filename
    7266335