    Performance of a CO2 water to water heat pump with less charge: Inlet temperature effects

  • Author

    Paul Maina;Zhongjie Huan

  • Author_Institution
    Department of Mechanical Engineering, Mechatronics and Industrial Design in Tshwane University of Technology, Box X680, Pretoria, 0001, South Africa
  • fYear
    2015
  • Firstpage
    239
  • Lastpage
    245
  • Abstract
    A CO2 water to water heat pump system was used to investigate the effects of cooling and chilling water inlet temperature at reduced charge capacity (approximately 75% of the full charge). The temperature were adjusted between 10 °C to 30 °C in nine steps while the throttle valve opening adjusted between 100%, 50% and 25%. It was observed that the as the cooling water inlet temperature increased, the heat output and general performance of the system diminished but as the chilling water temperature increased, there was an improvement of the system performance. Therefore, the best temperature combination was cooling - chilling water temperature of 10 °C - 30 °C. The opposite, i.e. cooling - chilling water temperature of 30 °C - 10 °C was the worst. Nevertheless, the effects of the cooling water temperature were higher on the system performance than the effect of the chilling water temperature. These observations were true in all throttle valve settings, where, the smaller the throttle valve opening, the higher the performance.