DocumentCode :
3662069
Title :
A synchronverter to damp electromechanical oscillations in the Brazilian transmission grid
Author :
E. L. van Emmerik;B. W. França;M. Aredes
Author_Institution :
LEMT - Power Electronics and Medium Voltage Laboratory of COPPE-POLI, UFRJ, Rio de Janeiro, Brazil
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
221
Lastpage :
226
Abstract :
Nowadays a SVC at the Bom Jesus da Lapa (BJL) substation (250 MVAr) is utilized to control voltage at the Southeast/Northeast interconnection. This paper has two purposes. One is to show the technical possibility to substitute the Static VAR Compensator (SVC) by a synchronverter. Secondly, that the synchronverter mitigates electromechanical oscillations. A control strategy is utilized to damp the North/South mode in the same way as a Power System Stabilizer (PSS), based on the power flow on a transmission line at a distance of more than 1000 km.
Keywords :
"Oscillators","Integrated circuit interconnections","Voltage control","Transmission line measurements","Power transmission lines","Inverters","Damping"