DocumentCode :
3662268
Title :
A single-phase PLL algorithm with disturbances immunity
Author :
Renato Guerreiro Araújo;Francisco Kleber A. Lima;João Amin M. Neto;Carlos Gustavo C. Branco
Author_Institution :
Department of Electrical Engineering, Federal University of Ceara, UFC, Fortaleza, Brazil
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
1496
Lastpage :
1501
Abstract :
This paper proposes a new closed-loop synchronization algorithm, PLL (Phase-Locked Loop), for applications in power conditioner systems for single-phase networks. The structure presented is based on the correlation of the input signal with a complex signal generated from the use of an adaptive filter in a PLL algorithm in order to minimize the computational effort. Moreover, the adapted PLL presents a higher level of rejection for two particular disturbances: interharmonic and subharmonic, when compared to the original algorithm. Simulation and experimental results will be presented in order to prove the efficacy of the proposed adaptive algorithm.
Keywords :
"Phase locked loops","Synchronization","Adaptive filters","Distortion","Frequency estimation","Harmonic analysis","Power harmonic filters"
Publisher :
ieee
Conference_Titel :
Industrial Electronics (ISIE), 2015 IEEE 24th International Symposium on
Electronic_ISBN :
2163-5145
Type :
conf
DOI :
10.1109/ISIE.2015.7281695
Filename :
7281695
Link To Document :
بازگشت