DocumentCode
3665219
Title
Testing and enhancement of the dynamic performance of a Phasor measurement unit
Author
Dinesh Rangana Gurusinghe;Athula D. Rajapakse;Krish Narendra
Author_Institution
Electrical and Computer Engineering, University of Manitoba, Winnipeg, MB R3T 2N2, Canada
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
1
Abstract
Phasor measurement units (PMUs) provide the basis for synchrophasor measurements, which are good data sources for capturing power system dynamic behavior. The recently published IEEE Standard C37.118.1-2011 characterizes the dynamic performance of synchrophasor measurements with two performance class filters: P-class and M-class. Practical implementation of a PMU to meet all dynamic requirements is a challenging task. Performance of an actual PMU with the proposed reference performance class filters is presented with a brief overview of the PMU performance evaluation process and the sources of errors in the test environment. Based on the test results, some inadequacies in the reference M-class filter algorithm provided in the standard are revealed, and several minor inconsistencies in the error limits imposed by the standard are highlighted. Finally, some modifications to the M-class reference filter and suggestions to rectify the minor issues in the new standard are proposed.
Keywords
"Phasor measurement units","Power system dynamics","Filtering algorithms","Standards","Testing","Computers","Power measurement"