Abstract :
This paper analyzes the response of conventional protection schemes (Line current Differential and Mho Distance elements) and the supervisory elements associated with those protective elements in commercial relays for Type 3 (Doubly Fed Induction Generator based) grid integrated wind farms. The response of line protection elements and their supervisory elements are analyzed using real time by hardware-in-the-loop simulation and differences from the behavior in case of conventional power systems are pointed. Faults are analyzed from the relay´s perspective and the observed behavior is elaborated upon. Challenges associated in using sequence components and relay sensitivity are discussed.
Keywords :
"Relays","Circuit faults","Rotors","Wind turbines","Wind farms","Power conversion"