DocumentCode
3665291
Title
Estimating dynamic model parameters for adaptive protection and control in power system
Author
Ariff Mam;Bikash Pal;Abhinav Singh
Author_Institution
Electrical, Imperial College London, U. K.
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
1
Abstract
Summary form only given. This paper presents a new approach in estimating important parameters of power system transient stability model such as inertia constant $H$ and direct axis transient reactance $x_{d}^{prime}$ in real time. It uses a variation of unscented Kalman filter (UKF) on the phasor measurement unit (PMU) data. The accurate estimation of these parameters is very important for assessing the stability and tuning the adaptive protection system on power swing relays. The effectiveness of the method is demonstrated in a simulated data from 16-machine 68-bus system model. The paper also presents the performance comparison between the UKF and EKF method in estimating the parameters. The robustness of method is further validated in the presence of noise that is likely to be in the PMU data in reality.
Keywords
"Adaptation models","Power system stability","Phasor measurement units","Adaptive systems","Power system transients","Stability analysis","Power system dynamics"
Publisher
ieee
Conference_Titel
Power & Energy Society General Meeting, 2015 IEEE
ISSN
1932-5517
Type
conf
DOI
10.1109/PESGM.2015.7285733