DocumentCode
3665657
Title
The need for a new generation of var meters
Author
Tan Zhang;John A. Orr;Alexander E. Emanuel
Author_Institution
Department of Electrical and Computer Engineering, Worcester, MA 01609, USA
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
5
Abstract
This study extends previous work on the appropriate definition of reactive power in the presence of harmonic voltages and currents to the three-phase, unbalanced case. As in the single phase case, it is advocated that reactive power be defined in terms of the fundamental components (60/50 Hz) of the current and the phase angle separating them. It is demonstrated that common metering techniques for reactive power in the presence of harmonics yield inaccurate results, with errors as great as 200%. Modern digital instrumentation is able to conveniently calculate correct values so the time has arrived to start improvements in the design of a new generation of var meters through comprehensive implementation of these digital techniques.
Keywords
"Reactive power","Harmonic analysis","Power measurement","Voltage measurement","Power system harmonics","Current measurement"
Publisher
ieee
Conference_Titel
Power & Energy Society General Meeting, 2015 IEEE
ISSN
1932-5517
Type
conf
DOI
10.1109/PESGM.2015.7286119
Filename
7286119
Link To Document