DocumentCode
3665723
Title
Secondary arc modelling for single pole reclosing analyses
Author
Jacek Klucznik;Zbigniew Lubosny;Krzysztof Dobrzynski;Stanislaw Czapp
Author_Institution
Faculty of Electrical and Control Engineering, Gdansk University of Technology, Poland
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
5
Abstract
The paper discusses two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage calculation results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a nonlinear secondary arc model implementation is presented. The paper presents the study results for the three types of EHV transmission lines: single circuit, double circuit and double circuit with shunt reactors. The authors indicate, that precise representation of secondary electric arc in power system studies can lead to different conclusion than analysis carried out on simplified arc models.