DocumentCode :
3665808
Title :
Factory acceptance test of a five-terminal MMC control and protection system using hardware-in-the-loop method
Author :
Gang Li; Yunlong Dong; Jie Tian; Weihua Wang; Wei Li;Jean Belanger
Author_Institution :
Research and development Institute, NR Electric, Nanjing, China
fYear :
2015
fDate :
7/1/2015 12:00:00 AM
Firstpage :
1
Lastpage :
5
Abstract :
Being the first five-terminal Modular Multilevel Converter (MMC)-based HVDC project in the world, the control and protection system must be validated under various operation modes as well as contingency at the factory acceptance test. This paper presents the configuration and performance of a hardware-in-the-loop (HIL) test platform that is based on a multi-rate real-time simulator using commercial-off-the-shelf architecture. The MMC sub-module model is implemented in field programmable gate array (FPGA) boards with a computation cycle of 500 ns, while the rest of the power system is simulated on the central processing unit (standard multi-core CPU) with a time-step of 30 μs. The State-space Nodal (SSN) interface is used to couple the models simulated on FPGA and on CPU. In addition, a communication protocol based on Giga-bit Ethernet is designed to connect the actual valve balancing controller with the real-time simulator. Results from the factory acceptance test are presented in this paper.
Keywords :
"Mathematical model","Voltage control","Valves","Real-time systems","Field programmable gate arrays","HVDC transmission","Circuit faults"
Publisher :
ieee
Conference_Titel :
Power & Energy Society General Meeting, 2015 IEEE
ISSN :
1932-5517
Type :
conf
DOI :
10.1109/PESGM.2015.7286275
Filename :
7286275
Link To Document :
بازگشت