DocumentCode :
3666899
Title :
Analysis of the influence to fault detecting of DC system from distributed capacitance
Author :
Dong Zhiyun;Lei Xing;Liu Gaoyuan;Ding Hongnin;Xu Zhaode
Author_Institution :
Maintenance Company, Shanghai Municipal Electric Power Company, Shanghai, China
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
1818
Lastpage :
1822
Abstract :
Inject signal is the most popular method used for fault detecting in the DC system. However, it usually misjudges faults due to the existence of distributed capacitance in substations. In this paper, the EHV substation secondary cable laying is considered, and typical capacitance and resistance values of secondary cable to the ground are used. We analyse the influence of distributed capacitance on fault detection when the injected signal is a low-frequency square wave. And then the integral method based on the inject signal is proposed, which can distinguish fault branches from non-fault branches. Furthermore, the influence of the time constant and injected signal frequency is discussed.
Keywords :
"Grounding","Capacitance","Resistance","Relays","Insulation","Substations","Circuit faults"
Publisher :
ieee
Conference_Titel :
Cyber Technology in Automation, Control, and Intelligent Systems (CYBER), 2015 IEEE International Conference on
Print_ISBN :
978-1-4799-8728-3
Type :
conf
DOI :
10.1109/CYBER.2015.7288223
Filename :
7288223
Link To Document :