    This paper present the experimental results of electrical breakdown time delay of commercial gas-filled surge arresters manufactured by CITEL, SIEMENS and EPCOS as a function of relaxation time τ (memory curve) and applied voltage Uw. It was shown that for CITEL components mean value of electrical breakdown time delay, td insignificantly changes up to τ ≈ 700ms. For 700 ms <; τ <; 3×103 ms, td value rapidly increases and for τ 3 10 ms > × 3td reaches saturation. Irradiation of CITEL components by gamma ray irradiation leads to significant decrease of td value for τ > 700ms. On the other hand, SIEMENS and EPCOS components show constant increase in td with the increase of τ until τ > 1s, when td value reaches saturation. The increase of applied voltage leads to significant decrease in td values up to Uw ≈ 300 V for all of the components, while for higher voltages such decrease is very small. Post-discharge mechanisms responsible for electrical breakdown time delay in these components were also analyzed.