Title :
Frequency and time domain calibration for large Rogowski coils
Author :
S. L. Combrink;P. G. Wiid
Author_Institution :
Department Electrical and Electronical Engineering, Stellenbosch University, Cnr of Banghoek&
Abstract :
The SKA needs strong mitigation measures to ensure a radio quiet environment. In an ongoing study, lightning induced RFI is investigated as well as a means to measure and mitigate its effects. The Rogowski coil is chosen as the principle current transducer and its calibration is studied. A time domain calibration approach is investigated and verified with a commercial current probe´s calibration data. This approach along with larger Rogowski coils requires an enlarged fixture for calibration. The larger fixtures introduce a mismatch resulting in high reflection loss. Simulations show that by using a dielectric with high permittivity in the calibration fixture a smaller fixture is realisable.
Keywords :
"Calibration","Coils","Probes","Current measurement","Conductors","Impedance","Bandwidth"
Conference_Titel :
Electromagnetics in Advanced Applications (ICEAA), 2015 International Conference on
DOI :
10.1109/ICEAA.2015.7297263