DocumentCode :
3679377
Title :
Design and implementation of a DC line-interactive uninterruptible power supply (UPS) with load leveling
Author :
Seyed Ahmad Hamidi;Jason S Katcha;Adel Nasiri
Author_Institution :
Center for Sustainable Electrical Energy Systems, University of Wisconsin-Milwaukee Milwaukee, USA
fYear :
2015
Firstpage :
1248
Lastpage :
1254
Abstract :
In this paper a novel DC line-interactive uninterruptable power supply (UPS) with load leveling feature is proposed. The new UPS replaces the common AC three phase UPS and can be used for systems with pulse loads, and has superiority in performance and efficiency. The DC UPS utilizes Li-ion battery module in the DC link to perform the load leveling feature and UPS functionality. A Li-ion LFP based battery module is developed and tested along with associated management system. The proposed system operates in four operating modes. Performance of the system in one of the modes is discussed. A dual-loop control scheme is used to manage the performance of the system in various modes. Simulation results are provided to verify the performance of the proposed system.
Keywords :
"Uninterruptible power systems","Batteries","Generators","Voltage control","Reliability","Rectifiers","Mathematical model"
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2015 IEEE
ISSN :
2329-3721
Electronic_ISBN :
2329-3748
Type :
conf
DOI :
10.1109/ECCE.2015.7309835
Filename :
7309835
Link To Document :
بازگشت