DocumentCode :
3680075
Title :
Input impedance based nyquist stability criterion for subsynchronous resonance analysis in DFIG based wind farms
Author :
Selam Chernet;Massimo Bongiorno
Author_Institution :
Dept. Energy and Environment, Chalmers University of Technology 412 96 Gothenburg, Sweden
fYear :
2015
Firstpage :
6285
Lastpage :
6292
Abstract :
One of the problems encountered when a wind farm is radially connected to a series compensated transmission line is subsynchronous resonance (SSR). The aim of this paper is to investigate the risk of SSR condition in Doubly-Fed Induction Generator (DFIG) based wind farms that are radially connected to series compensated transmission lines. The IEEE First Benchmark Model (IEEE FBM) is adopted and the passivity of the system in the subsynchronous range is investigated. Impedance based Nyquist criterion is used to assess the impact of DFIG controller parameters, output power and compensation level. The obtained analytical results are verified using time-domain simulation in PSCAD/ EMTDC.
Keywords :
"Impedance","Power transmission lines","Rotors","Wind farms","Mathematical model","Admittance","Stators"
Publisher :
ieee
Conference_Titel :
Energy Conversion Congress and Exposition (ECCE), 2015 IEEE
ISSN :
2329-3721
Electronic_ISBN :
2329-3748
Type :
conf
DOI :
10.1109/ECCE.2015.7310541