Title :
Improvement of the ground-fault detection in field windings of synchronous machines with static excitation based on third-harmonic voltage phase-angle comparison
Author :
Francisco R. Blánquez;Carlos A. Platero;E. Rebollo;F. Blázquez
Author_Institution :
Department of Electrical Engineering, ETSII - Polytechnic University of Madrid, Madrid, Spain
fYear :
2015
Firstpage :
1
Lastpage :
9
Abstract :
This paper presents the theoretical approach and experimental tests of a new algorithm for detecting ground faults in rotor windings of synchronous generators with static excitation. This location method requires the installation of a grounding resistance in the secondary winding of the excitation transformer. First, the third-harmonic reference voltage is obtained by the voltage measurements in the excitation system. Then, the third-harmonic voltage at the grounding resistor is compared to the reference voltage. The ground fault is detected when the phase angle between those voltages is under the trip setting value. This new algorithm has been tested in a 5 kVA Synchronous generator with satisfactory results.
Keywords :
"Windings","Circuit faults","Voltage measurement","Grounding","Rotors","Resistance","Synchronous generators"
Publisher :
ieee
Conference_Titel :
Power Electronics and Applications (EPE´15 ECCE-Europe), 2015 17th European Conference on
Type :
conf
DOI :
10.1109/EPE.2015.7311685
Filename :
7311685