DocumentCode :
3680835
Title :
Limitations of the H-bridge multilevel STATCOMs in compensation of current imbalance
Author :
Duro Basic;Martin Geske;Stefan Schroeder
Author_Institution :
General Electric, Power Conversion, Culemeyerstrase 1, 12277 Berlin, Germany
fYear :
2015
Firstpage :
1
Lastpage :
10
Abstract :
In this paper we investigate limitations of H-bridge multilevel STATCOMs in the compensation of current imbalance in industrial applications. In either star or delta topology of the STATCOM converters, the zero sequence injection is used to balance power flows (i.e. to balance dc bus capacitor voltages) in the arm converters. In imbalanced situations the compensation capability of the current imbalance is limited by the level of the required zero sequence injection.
Keywords :
"Topology","Automatic voltage control","Bridge circuits","Load flow","Facsimile","Electronic mail"
Publisher :
ieee
Conference_Titel :
Power Electronics and Applications (EPE´15 ECCE-Europe), 2015 17th European Conference on
Type :
conf
DOI :
10.1109/EPE.2015.7311687
Filename :
7311687
Link To Document :