DocumentCode :
3683284
Title :
Effect of the diesel engine delay on stability of isolated power systems with high levels of renewable energy penetration
Author :
Dusan Nikolic;Michael Negnevitsky;Martin de Groot
Author_Institution :
Member IEEE, Hydro Tasmania, Hobart, Australia
fYear :
2015
Firstpage :
70
Lastpage :
73
Abstract :
Isolated power systems (IPSs) up to 20MW capacity are traditionally based on diesel generators. Due to the high cost of diesel fuel supply, as well as environmental concerns, IPSs are increasingly integrating renewable generation. Since traditional diesel generation was built for slow changing, diesel-only systems some IPSs might experience problems in the future, while trying to support fast-changing, intermittent renewable generation. This paper argues that engine delay, together with the governor and inertia, has to be considered when designing a high renewable penetration IPS based on diesel generators for reserve capacity. Our simulation results show that some diesel generators have advantage over others in governing the system and preserving power system stability.
Keywords :
"Generators","Diesel engines","Delays","Power system stability","Mathematical model","Fuels"
Publisher :
ieee
Conference_Titel :
Smart Electric Distribution Systems and Technologies (EDST), 2015 International Symposium on
Type :
conf
DOI :
10.1109/SEDST.2015.7315185
Filename :
7315185
Link To Document :