DocumentCode
3696384
Title
New configuration constraints to reduce unbalance in hexagonal double-circuit transmission lines
Author
Al-Motasem I. Aldaoudeyeh;F. K. Amoura;Hussein M. Al-Masri;Ahmad Abuelrub
Author_Institution
Yarmouk University, Irbid, Jordan
fYear
2015
Firstpage
1
Lastpage
6
Abstract
Mutual impedances of transmission lines are not equal due to unequal spacing between conductors which creates problems like circulating current in double circuit lines. In this paper, the authors introduce novel configurations constraints for hexagonal double circuit arrangement that will achieve equal mutual impedances without transposition. Principal results of such arrangement are uncoupling between positive, negative and zero sequence networks, minimizing negative and zero sequence unbalance values, and increasing line loadability. Impact of adding one and two ground wires on the proposed configuration is also evaluated.
Keywords
"Conductors","Wires","Power transmission lines","Earth","Transmission line matrix methods","Impedance","Resistance"
Publisher
ieee
Conference_Titel
North American Power Symposium (NAPS), 2015
Type
conf
DOI
10.1109/NAPS.2015.7335112
Filename
7335112
Link To Document