DocumentCode
3696476
Title
A study on the effect of the high-penetration photovoltaic system on an increase in overvoltage of distribution feeders
Author
Insu Kim;Ronald G. Harley
Author_Institution
Electrical Engineering, Alabama A&
fYear
2015
Firstpage
1
Lastpage
4
Abstract
The objective of this study is to investigate the transient behavior of a distribution network when photovoltaic (PV) systems with relatively high capacity are injecting their power. Therefore, using DIgSILENT, this study models a substation distribution system, including feeder J1 with 3,434 buses in the northeastern United States, adds four PV systems with relatively high capacity (28.8 percent of peak generation of the substation), and examines transient responses of the feeder when PV systems either able or unable to control reactive power are injecting their power.
Keywords
"Reactive power","Voltage control","Substations","Transient analysis","Photovoltaic systems","Analytical models"
Publisher
ieee
Conference_Titel
North American Power Symposium (NAPS), 2015
Type
conf
DOI
10.1109/NAPS.2015.7335204
Filename