DocumentCode
3699382
Title
Analysis of shielding failure in transmission lines considering both first and subsequent strokes
Author
Rafael Alipio;Rosilene N. Dias;Silverio Visacro;Fernando H. Silveira
Author_Institution
Federal Center of Technical Education of Minas Gerais, Department of Electrical Engineering, Belo Horizonte, Brazil
fYear
2015
Firstpage
215
Lastpage
220
Abstract
This work asses the shielding failure of transmission lines by applying the Electrogeometric Model, notably considering the influence of both first and subsequent strokes and also channel angles different from 0° (vertical channel). Considering different tower geometries, it is shown that the shielding failure rate of transmission lines is much more significant for subsequent strokes than for first stroke currents. Furthermore, it is shown that considering channel angles different from 0° leads to an increase of the number of strokes hitting phase conductors. Such increase can be very significant depending on the tower geometry, for instance, in case of EHV double circuit lines.
Keywords
"Heating","Cable shielding"
Publisher
ieee
Conference_Titel
Lightning Protection (XIII SIPDA), 2015 International Symposium on
Type
conf
DOI
10.1109/SIPDA.2015.7339314
Filename
7339314
Link To Document