DocumentCode
3708361
Title
A novel method to clean aged RTV coating before recoating
Author
Xiangyun Fu; Zhifu Zhang; He Gao; Xiangjun Lin; Bin Cao; Hongwei Mei; Liming Wang
Author_Institution
State Grid Lianyungang Power Supply Company, Jiangsu Province, 222000, China
fYear
2015
Firstpage
717
Lastpage
720
Abstract
RTV (Room Temperature Vulcanizing silicone rubber) is widely applied in power grids in China to prevent serious pollution flashover accident on the porcelain and glass insulators. The aging of RTV coating inclines to decrease anti-pollution flashover performance of the coating insulators, so the RTV coating need to be repaired after a period of operation time. The mechanical properties of RTV (such as the adhesion) will not be improved if recoating new RTV coating without cleaning the contamination and the aged RTV coating on the insulator surface and the life cycle of recoating RTV will be shortened. This article proposes a novel method to clean the contamination and aged RTV coating before recoating. Based on this method, the quality of recoating RTV coating is improved and the construction period of recoating is greatly shortened. The results of the adhesion tests show that this method to clean the age RTV coating is effective and has potential value in engineering practice.
Keywords
"Coatings","Aging","Insulators","Surface treatment","Surface contamination","Adhesives"
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2015 IEEE Conference on
Print_ISBN
978-1-4673-7496-5
Type
conf
DOI
10.1109/CEIDP.2015.7351991
Filename
7351991
Link To Document