• DocumentCode
    3708419
  • Title

    Aging effect on oil cooling capacity of a non-guided disc windings power transformer

  • Author

    K. S. Kassi;I. Fofana;M. I. Farinas;C. Volat

  • Author_Institution
    Insulating Liquids and Mixed Dielectrics for Electrotechnology (ISOLIME), Universit? du Qu?bec ? Chicoutimi, Canada
  • fYear
    2015
  • Firstpage
    804
  • Lastpage
    807
  • Abstract
    Many transformers around the world are serving close to or beyond their design life. In these important asset, cores and coils losses cause heating and energy losses within the core decreasing their efficiency and shortening their life expectancy. The aim of this contribution was to study the aging effect on mineral oil cooling capacity of power transformers. The oil aging effect on its viscosity and its physicochemical properties is also reported. A 2D axisymmetric thermo-fluid numerical model was developed with COMSOL Multiphysics to study the cooling capability of oil aged at different levels. The results show that the oil viscosity increase considerably with aging and its physicochemical properties are also affected. It was found that sludge as oil oxidation byproduct contributes to the widening of hot spots in the transformers with non-guided disc windings.
  • Keywords
    "Aging","Viscosity","Power transformer insulation","Oil insulation","Mathematical model"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2015 IEEE Conference on
  • Print_ISBN
    978-1-4673-7496-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2015.7352049
  • Filename
    7352049