• DocumentCode
    3712126
  • Title

    Installation, startup and performance of a static var compensator for an electric arc furnace upgrade

  • Author

    Sam Morello;Thomas J. Dionise;Thomas L. Mank

  • Author_Institution
    ARM EnerTech Associates, LLC, Johnstown, PA
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    9
  • Abstract
    This steel maker upgraded the Electric Arc Furnace (EAF) Melt Shop to increase production and improve metallurgical quality of their product. The increased electrical load and harmonic generation for the new furnace operation necessitated the installation of a 80 MVAR static var compensator (SVC) to meet utility interconnect requirements. This paper is a follow-up and companion to [1] that documented comprehensive analysis to specify the SVC. This paper describes the sequence of events during the installation, commissioning and operation of the SVC. It will assess the performance of the SVC compared to the electrical requirements of the utility for voltage regulation, flicker, harmonics and power factor. Power quality measurements during EAF operation without the SVC established a baseline to from which to show improvements provided by the SVC as well as compliance with the utility limits. Additionally, events encountered during the commissioning are shared as lessons learned.
  • Keywords
    "Decision support systems","Furnaces","Static Var compensators","Harmonic analysis","Flicker"
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2015 IEEE
  • Type

    conf

  • DOI
    10.1109/IAS.2015.7356881
  • Filename
    7356881