DocumentCode
3712191
Title
A method of 20 kV cable line fault location based on sheath grounding current
Author
Faan Guo;Guofang Zhu;Xiaofeng Dong
Author_Institution
School of Electrical Engineering, Shandong University, Jingshi Road NO.17923, 250061 Jinan, Shandong, China
fYear
2015
Firstpage
1
Lastpage
5
Abstract
To solve the problem of fault location in 20 kV medium-voltage distribution network cable line, a method based on sheath grounding current is presented in this paper. When unsymmetrical earth fault occurs, the sheath grounding current contains three ingredients. After analyzing the relationship between induced circulating current flowing in cable sheath and zero-sequence current flowing in the cable core, it is found that the sheath grounding current has characteristics obvious enough to distinguish internal or external fault type. Based on this, sheath grounding current overflowing criterion is proposed which is effective to locate the fault section of cable line. At last, validity of the sheath grounding current overflowing criterion is verified by RTDS simulation results.
Keywords
"Fault diagnosis","Voltage measurement","Grounding","Power cables"
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting, 2015 IEEE
Type
conf
DOI
10.1109/IAS.2015.7356949
Filename
7356949
Link To Document