DocumentCode :
3720357
Title :
New standard for electrical grid reliability and energy efficiency. Commercially available fault current limiters enable cost-effective connection of generation and distributed renewable energy sources to transmission, distribution and industrial networks
Author :
Uri Garbi;Mohinder Pannu
Author_Institution :
GridON Ltd., Givatayim, Israel
fYear :
2015
Firstpage :
226
Lastpage :
228
Abstract :
GridON´s saturated core fault current limiters have been installed in live networks for more than two years. Field performance and test results of 10MVA and 30MVA devices are described in this paper. These saturated core fault current limiters (FCLs) are passive failsafe devices, which limit the fault current from the first peak and have immediate recovery capability. They present a large ratio between fault impedance and normal impedance, based solely on the current level through them. These FCLs are now well-established field proven devices and commercially available products. The paper reviews the performance of these devices through long duration and high power fault events. Their uninterrupted operation in transformer feeders is demonstrated. These FCLs are based on standard power transformer technology and are scalable to all voltage levels up to EHV transmission networks.
Keywords :
"Circuit faults","Fault currents","Impedance","Substations","Fault current limiters","Performance evaluation","Power transformers"
Publisher :
ieee
Conference_Titel :
Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
Type :
conf
DOI :
10.1109/ICEPE-ST.2015.7368371
Filename :
7368371