• DocumentCode
    3720397
  • Title

    Capacitive current breaking capability estimation for a 145 kV 40 kA GIS circuit breaker

  • Author

    Sead Deli?;Dejan Be?lija;Dalibor Gorenc;Armin Hajdarovi?;Mirsad Kapetanovi?

  • Author_Institution
    Faculty of Electrical Engeenering Sarajevo, University of Sarajevo
  • fYear
    2015
  • Firstpage
    74
  • Lastpage
    78
  • Abstract
    In this paper, the impact of several 145 kV 40 kA GIS (Gas Insulated Switchgear) circuit breaker design parameters, such as length of the main nozzle throat, contact travel and average opening speed, on the estimated breakdown voltage of the contact gap of an interrupter during capacitive current breaking is analyzed. A new approach for breakdown voltage estimation, which provides full correlation between all circuit breaker design parameters and dielectric characteristics of the contact gap and the criterion for breakdown occurrence, was used for this purpose. The estimated capacitive current breaking capability of the circuit breaker was verified by type testing in KEMA High Power Laboratory, the Netherlands.
  • Keywords
    "Circuit breakers","Gas insulation","Interrupters","Dielectrics","Estimation","Electric fields","Testing"
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2015.7368412
  • Filename
    7368412