DocumentCode :
3720400
Title :
Interruption simulation at different arcing times for a puffer type 252kV SF6 circuit breaker
Author :
Jin Guo;Xu Jiang;Bing Chen;Jingwei Mu
Author_Institution :
Xi´an high voltage apparatus research institute co., Ltd Xi´an, China
fYear :
2015
Firstpage :
345
Lastpage :
348
Abstract :
In this paper, an interruption simulation model for 252kV SF6 Circuit Breaker is built according to MHD theory. Through the calculation, the distributions of the arc column temperature and flow field during the interruption process are acquired considering two different arcing times. The gas pressure, temperature and voltage of the arc plasma in different arcing times are presented. Two analysis points at the pressure cylinder and the nozzle throat are observed. Relationships between dynamic arc plasma characteristics and different arcing times are analyzed. The simulation results show that the arc burning 14ms is easier to extinguish.
Keywords :
"Circuit breakers","Interrupters","Temperature","Sulfur hexafluoride","Integrated circuit modeling","Plasma temperature"
Publisher :
ieee
Conference_Titel :
Electric Power Equipment ? Switching Technology (ICEPE-ST), 2015 3rd International Conference on
Type :
conf
DOI :
10.1109/ICEPE-ST.2015.7368415
Filename :
7368415