DocumentCode :
3724241
Title :
Modified Synchronous Reference Frame Method for Active Power Filter under Asymmetric and Distorted Supply Voltages Condition
Author :
Xiangshun Li;Hongliang He;Jianghua Lu;Zhiwei Liang
Author_Institution :
Sch. of Autom., Wuhan Univ. of Technol. Wuhan, Wuhan, China
fYear :
2015
Firstpage :
1
Lastpage :
5
Abstract :
In this paper, a modified harmonic and reactive current detection method based on synchronous reference frame (SRF) theory for three-phase four-wire shunt active power filter (SAPF) is proposed under distorted supply voltages condition. The main objective of the method is to extract the fundamental positive-sequence active currents, which can compensate the fundamental positive sequence reactive components, the unbalanced components and harmonics of the load currents. A model of three-phase four-leg SAPF with LCL-filter based on the proposed SRF method has been designed and simulated on MATLAB/simulink. Simulation results indicate that not only the current total harmonic distortion (THDi) values for each phase of the supply currents are reduced from 21.71%, 22.37% and 20.82% to 4.56%, 4.67% and 4.58%, but also the supply currents are balanced and sinusoidal after compensation.
Keywords :
"Harmonic analysis","Power harmonic filters","Active filters","Harmonic distortion","Reactive power","Phase distortion"
Publisher :
ieee
Conference_Titel :
Industrial Informatics - Computing Technology, Intelligent Technology, Industrial Information Integration (ICIICII), 2015 International Conference on
Type :
conf
DOI :
10.1109/ICIICII.2015.88
Filename :
7373776
Link To Document :
بازگشت