• DocumentCode
    3725008
  • Title

    Frequency response measurement of a power transformer

  • Author

    W. G. Ariastina;I N. S. Kumara;C. G. Indra Partha;I G. Dyana Arjana;I W. Arta Wijaya;A. A. N. Amrita;I. A. D. Giriantari

  • Author_Institution
    Department of Electrical and Computer Engineering, Udayana University, Bali-80362, Indonesia
  • fYear
    2015
  • Firstpage
    102
  • Lastpage
    105
  • Abstract
    This paper presents a field experience in condition monitoring of a power transformer using SFRA technique. A design based comparison approach of the SFRA test results is discussed in the paper. In order to verify the latest condition of the transformer, the SFRA test was complemented with DGA and PD tests. The SFRA test results indicated that there is an abnormality within the transformer windings. The PD test results confirmed this interpretation, where very large ultrasonic impulses were detected. A series of DGA tests have showed that there is an early stage degradation of the insulating paper, which may be associated with fault within the transformer windings. The field experience showed that the monitoring approach has been very useful in indicating the possible occurrence of failure within the transformer structure.
  • Keywords
    "Windings","Frequency measurement","Frequency response","Power transformer insulation","Resonant frequency","Oil insulation"
  • Publisher
    ieee
  • Conference_Titel
    Quality in Research (QiR), 2015 International Conference on
  • Print_ISBN
    978-1-4799-6550-2
  • Type

    conf

  • DOI
    10.1109/QiR.2015.7374905
  • Filename
    7374905