DocumentCode :
3729685
Title :
Insulation status diagnosis of XLPE cable based on polarization and depolarization current (PDC)
Author :
Aixuan Zhao;Yanbo Wang;Xing Zhang;Junbo Deng;Guanjun Zhang;Shiyan Tao;Linlin Wu
Author_Institution :
State Key Laboratory of Electrical Insulation and Power Equipment, Xi´an Jiaotong University, Xi´an, China
fYear :
2015
Firstpage :
1
Lastpage :
5
Abstract :
Cross-linked polyethylene (XLPE) insulation cable is widely used in distribution power system, so it is important to reasonably estimate cable insulation status. Cable insulation is mainly affected by high temperature and water tree. Therefore, in this paper, we use PDC method to evaluate cable insulation, which is non-destructive due to its low voltage. In order to find out the relationship between PDC curve and aging status, we put 5 single-core cable samples in oven and set aging temperature as 14°C. Then, we divide these samples into different aging time (new, 10 days, 20 days, 30 days, 40 days) and measure the PDC curve. The result shows that with the increase of aging time, the PDC curve decreases quicker and the absolute value of steady current becomes higher. PDC will be a very practical way to judge cable insulation in the future.
Keywords :
"Aging","Power cables","Power cable insulation","Current measurement","Partial discharges"
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2015 IEEE PES Asia-Pacific
Type :
conf
DOI :
10.1109/APPEEC.2015.7380983
Filename :
7380983
Link To Document :
بازگشت