• DocumentCode
    3730806
  • Title

    Development of a cooling control system for data centers utilizing indirect fresh air based on Model Predictive Control

  • Author

    Masatoshi Ogawa;Hiroyuki Fukuda;Hiroyoshi Kodama;Hiroshi Endo;Toshio Sugimoto;Takeo Kasajima;Masao Kondo

  • Author_Institution
    FUJITSU LABORATORIES LTD., Kanagawa, Japan
  • fYear
    2015
  • Firstpage
    132
  • Lastpage
    137
  • Abstract
    In this paper, a cooling control system based on Model Predictive Control is developed in order to reduce energy consumption of the facility equipment for the modular data center utilizing indirect fresh air, while considering the relationship between energy savings and temperature management of servers. Furthermore, the developed cooling control system is applied to the actual modular data center utilizing indirect fresh air, and its practical effectiveness is verified by conducting a demonstration experiment. To develop the proposed control system, a dynamic mathematical model for the actual modular data center is designed, and the proposed control system is mounted on an existing management server. The control system is able to operate without using a separate hardware controller. As a result, it is revealed that the proposed control system reduces facility´s total power consumption by about 49% compared to a conventional system under condition where the supply air flow rate is 20°C.
  • Keywords
    "Servers","Mathematical model","Predictive models","Air conditioning"
  • Publisher
    ieee
  • Conference_Titel
    Ultra Modern Telecommunications and Control Systems and Workshops (ICUMT), 2015 7th International Congress on
  • Electronic_ISBN
    2157-0221
  • Type

    conf

  • DOI
    10.1109/ICUMT.2015.7382417
  • Filename
    7382417