DocumentCode
3733614
Title
Behavior of different distance relay characteristic on lines fed from type-1 and type-2 WTGU connected radially to grid: A case study
Author
Sachin Srivastava;Abhinna Biswal;K. S. V. Phanindra;U. J. Shenoy
Author_Institution
Power technologies, India development centre, ABB GISL, Bangalore, India
fYear
2015
Firstpage
1
Lastpage
6
Abstract
Line protection in HV/EHV/UHV lines is primarily by distance protection due to its selective, reliable and secure operation. With the wind farm penetration, the SIRs of lines are going to change drastically throughout the day. A case study has been performed in this paper to study the behavior of dynamic characteristics with respect to these changes. Analytically fault voltages and currents are calculated for the system. Distance relay implemented on hardware has been validated with these waveforms and inferences have been made to give recommendations for characteristics to be applied in practical systems for secure and reliable operation of distance relay.
Keywords
"Impedance","Protective relaying","Wind farms","Wind speed","Hardware","Fault currents"
Publisher
ieee
Conference_Titel
Smart Grid Technologies - Asia (ISGT ASIA), 2015 IEEE Innovative
Electronic_ISBN
2378-8542
Type
conf
DOI
10.1109/ISGT-Asia.2015.7387030
Filename
7387030
Link To Document