DocumentCode :
3733614
Title :
Behavior of different distance relay characteristic on lines fed from type-1 and type-2 WTGU connected radially to grid: A case study
Author :
Sachin Srivastava;Abhinna Biswal;K. S. V. Phanindra;U. J. Shenoy
Author_Institution :
Power technologies, India development centre, ABB GISL, Bangalore, India
fYear :
2015
Firstpage :
1
Lastpage :
6
Abstract :
Line protection in HV/EHV/UHV lines is primarily by distance protection due to its selective, reliable and secure operation. With the wind farm penetration, the SIRs of lines are going to change drastically throughout the day. A case study has been performed in this paper to study the behavior of dynamic characteristics with respect to these changes. Analytically fault voltages and currents are calculated for the system. Distance relay implemented on hardware has been validated with these waveforms and inferences have been made to give recommendations for characteristics to be applied in practical systems for secure and reliable operation of distance relay.
Keywords :
"Impedance","Protective relaying","Wind farms","Wind speed","Hardware","Fault currents"
Publisher :
ieee
Conference_Titel :
Smart Grid Technologies - Asia (ISGT ASIA), 2015 IEEE Innovative
Electronic_ISBN :
2378-8542
Type :
conf
DOI :
10.1109/ISGT-Asia.2015.7387030
Filename :
7387030
Link To Document :
بازگشت