DocumentCode :
3737055
Title :
Advanced nonintrusive load monitor for equipment diagnostics on fan coil unit
Author :
Buyun Jing;Mei Chen
Author_Institution :
TBS Group, United Technologies Research Center (China) Shanghai, China
fYear :
2015
Firstpage :
339
Lastpage :
344
Abstract :
Fand Coil Units (FCUs) are widely used in commercial buildings to provide heating and cooling; and are therefore important for equipment and energy diagnostics in buildings. Currently, there is no low-cost and high-performance diagnostics method for FCUs. This hinders the deployment of equipment and energy diagnostics for building automation systems and smart building services. In this paper, we propose a novel approach which integrates two independent systems - an advanced nonintrusive load monitoring (NILM+) system and a statistical model-based diagnostics system into a single FCU diagnostic concept. NILM+ provides critical information enabling FCU equipment diagnostic models to detect fan and coil valve faults within 5 minutes. The diagnostic algorithms yields false alarm rates less than 8% and missed detect rates less than 10%.
Keywords :
"Buildings","Monitoring","Power measurement","Gaussian distribution","Load modeling","Fans","Switches"
Publisher :
ieee
Conference_Titel :
Industrial Electronics Society, IECON 2015 - 41st Annual Conference of the IEEE
Type :
conf
DOI :
10.1109/IECON.2015.7392122
Filename :
7392122