• DocumentCode
    3737145
  • Title

    Suppression of arc grounding overvoltage by using ZnO nonlinear resistance grounding mode

  • Author

    Tan Wangjing;Wang Qian;Duan Jiandong;Ye Zan;Huang Jingjing

  • Author_Institution
    School of Automation and Information Engineering, Xi´an University of Technology, Xi´an, China
  • fYear
    2015
  • Firstpage
    899
  • Lastpage
    904
  • Abstract
    Developments in power capacity have made arc grounding overvoltage increasingly prominent. This paper proposes a new method for determining current-voltage (I-V) characteristics of ZnO nonlinear resistance on a new grounding mode, by analyzing the power system through the symmetrical component method, considering system capacities, operation mode, and other characteristics. Then, the I-V characteristics of ZnO nonlinear resistance are obtained through the segmental linearization method. Finally, a model based on an actual 10kV system is established, and the different grounding modes are compared and simulated by ATP-EMTP. Results indicate that the designed ZnO nonlinear resistance parameters can suppress arc grounding overvoltage, and the proposed grounding mode is safe and reliable.
  • Keywords
    "Grounding","Resistance","Voltage control","Zinc oxide","II-VI semiconductor materials","Impedance","Reliability"
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, IECON 2015 - 41st Annual Conference of the IEEE
  • Type

    conf

  • DOI
    10.1109/IECON.2015.7392213
  • Filename
    7392213