• DocumentCode
    3737187
  • Title

    Improved DFIG capability during asymmetrical grid faults

  • Author

    Dao Zhou;Frede Blaabjerg

  • Author_Institution
    Department of Energy Technology, Aalborg University, Pontoppidanstraede 101, Aalborg, DK-9220, Denmark
  • fYear
    2015
  • Firstpage
    1152
  • Lastpage
    1157
  • Abstract
    In the wind power application, different asymmetrical types of the grid fault can be categorized after the Y/d transformer, and the positive and negative components of a single-phase fault, phase-to-phase fault, and two-phase fault can be summarized. Due to the newly introduced negative and even the natural component of the Doubly-Fed Induction Generator (DFIG) stator flux during the fault period, their effects on the rotor voltage can be investigated. It is concluded that the phase-to-phase fault has the worst scenario due to its highest introduction of the negative stator flux. Afterwards, the capability of a 2 MW DFIG to ride through asymmetrical grid faults can be estimated at the existing design of the power electronics converter. Finally, a control scheme aimed to improve the DFIG capability is proposed and the simulation results validate its feasibility.
  • Keywords
    "Rotors","Stator windings","Resistance","Wind turbines","Inductance","Mathematical model"
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, IECON 2015 - 41st Annual Conference of the IEEE
  • Type

    conf

  • DOI
    10.1109/IECON.2015.7392255
  • Filename
    7392255