DocumentCode
3737522
Title
Output impedance mitigation at filter resonance for single and three-phase UPS systems with reduced sensor count
Author
Sanjay Tolani;Parthasarathi Sensarma
Author_Institution
Department of Electrical Engineering, Indian Institute of Technology, Kanpur 208016, India
fYear
2015
Firstpage
3206
Lastpage
3211
Abstract
Widespread deployment of Voltage Source Inverters (VSI-s) in high penetration applications like distributed generation, UPS and stand-alone renewable energy conditioning imposes stringent demands on reliability and output voltage regulation. Reported literature offers numerous solutions for output voltage regulation, which includes twin aspects of command tracking and output impedance control. Most of these methods rely on measurement of at least two separate variables per phase, which compromises overall reliability. This paper focuses on output voltage regulation approaches requiring measurement of a single variable, per phase. It is analytically shown that single-loop approaches are inadequate for satisfying both reference tracking and output impedance specifications. Subsequently, two new improvements using a multi-loop approach are proposed and performance of these techniques are predicted analytically. Experimental results are presented to confirm the validity of suggested approaches.
Keywords
"Voltage control","Resonant frequency","Gain","Impedance","Capacitors","Damping","Transfer functions"
Publisher
ieee
Conference_Titel
Industrial Electronics Society, IECON 2015 - 41st Annual Conference of the IEEE
Type
conf
DOI
10.1109/IECON.2015.7392594
Filename
7392594
Link To Document