• DocumentCode
    3738351
  • Title

    Assessing of the tripping effectiveness of fuses in electrical installation fed from a synchronous generator set

  • Author

    Ryszard Kozmian;Andrzej Kusz;Marek Kuna-Broniowski;Piotr Makarski;Marek Scibisz;Krzysztof Ludwinek;Roman Nadolski;Jan Staszak

  • Author_Institution
    Society of Energy Management, Lublin, Poland
  • fYear
    2015
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The paper presents a simply method for assessing the effectiveness of fast automatic disconnection of supply (electric shock protection) based on measurement of Joule´s integral and thermal equivalent current in 230/400 V electrical installations fed from a synchronous generator sets. Experimental studies are carried out under short-circuit conditions using Electronic Phase Detector and Joule Integral Measurement device utilizing 5.5 kVA salient pole synchronous generator protected by gF and gG class fuses.
  • Keywords
    "Fuses","Synchronous generators","Short-circuit currents","Electric shock","Current measurement","Impedance","Circuit faults"
  • Publisher
    ieee
  • Conference_Titel
    Selected Problems of Electrical Engineering and Electronics (WZEE), 2015
  • Type

    conf

  • DOI
    10.1109/WZEE.2015.7394011
  • Filename
    7394011