DocumentCode
3738351
Title
Assessing of the tripping effectiveness of fuses in electrical installation fed from a synchronous generator set
Author
Ryszard Kozmian;Andrzej Kusz;Marek Kuna-Broniowski;Piotr Makarski;Marek Scibisz;Krzysztof Ludwinek;Roman Nadolski;Jan Staszak
Author_Institution
Society of Energy Management, Lublin, Poland
fYear
2015
Firstpage
1
Lastpage
4
Abstract
The paper presents a simply method for assessing the effectiveness of fast automatic disconnection of supply (electric shock protection) based on measurement of Joule´s integral and thermal equivalent current in 230/400 V electrical installations fed from a synchronous generator sets. Experimental studies are carried out under short-circuit conditions using Electronic Phase Detector and Joule Integral Measurement device utilizing 5.5 kVA salient pole synchronous generator protected by gF and gG class fuses.
Keywords
"Fuses","Synchronous generators","Short-circuit currents","Electric shock","Current measurement","Impedance","Circuit faults"