• DocumentCode
    37469
  • Title

    Assessment of Spare Breaker Requirements for High Voltage Transmission Stations

  • Author

    Hamoud, G.A.

  • Author_Institution
    Hydro One Inc., Toronto, ON, Canada
  • Volume
    28
  • Issue
    4
  • fYear
    2013
  • fDate
    Nov. 2013
  • Firstpage
    4789
  • Lastpage
    4795
  • Abstract
    This paper describes a probabilistic method based on a total risk index (probability times consequences) for assessing the number of spare breakers required for a group of similar high voltage breakers used in switching and transformer stations. The proposed method uses a Markov model for assessing the probability of failures and a bulk power system reliability program for evaluating failure consequences. The method considers a number of factors such as the group size, unit failure rate, unit repair time, transmission station layout, and other power system parameters that may impact the number of spare breakers. A cost/benefit analysis approach is used in determining the required number of spare breakers. The number of spare units is determined when the total cost (sum of spare unit costs, system operating costs and system outage costs due to breaker failures) is minimum. An example is given to illustrate the proposed method of assessment.
  • Keywords
    Markov processes; circuit breakers; failure analysis; maintenance engineering; power transmission planning; power transmission protection; probability; redundancy; Markov model; breaker failure; failure consequence; group size; high voltage breaker; high voltage transmission stations; power system parameter; probabilistic method; probability times consequence; spare breaker requirement; spare units; switching station; total risk index; transformer station; transmission station layout; unit failure rate; unit repair time; Maintenance engineering; Markov processes; Power transformers; Probabilistic logic; Propagation losses; Sociology; Statistics; Bulk power system reliability; Markov model; cost/benefit analysis; failure rate; group availability; regular and spare breakers; system energy cost; system outage cost; transmission station;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2013.2271550
  • Filename
    6558858