• DocumentCode
    3748011
  • Title

    Assessing induced sheath voltage in multi-circuit cables: Revising the methodology

  • Author

    M. Shaban;M. A. Salam;S. P. Ang;M.A.B. Sidik;Z. Buntat;William Voon

  • Author_Institution
    Dept. of Electrical and Electronic Engineering, Faculty of Engineering, Institut Teknologi Brunei, Brunei Darussalam
  • fYear
    2015
  • Firstpage
    272
  • Lastpage
    276
  • Abstract
    Flow of current in a cable conductor generates a magnetic field which could induce current flow in the metallic cable shield or sheath. This paper examines induced voltage calculation in multi-circuit of the cables with the hope of proposing new methodology for induced sheath voltage computation in metallic shield of a single-core power cable operating in a triple circuit. This study considers a few examples to demonstrate the method of examining the induced voltage in single, double and triple-circuits. The calculated values for induced voltages were 0.079 V/m, 0.074 V/m and 0.068 V/m for triple, double and single circuit. It is found that induced sheath voltage increased with the increase in number of the cables.
  • Keywords
    "Power cables","Cable shielding","Mathematical model","Inductance","Conductors","Cable insulation","Magnetic fields"
  • Publisher
    ieee
  • Conference_Titel
    Energy Conversion (CENCON), 2015 IEEE Conference on
  • Type

    conf

  • DOI
    10.1109/CENCON.2015.7409553
  • Filename
    7409553