DocumentCode :
374889
Title :
Harmonic modeling of distorting loads on distribution feeders and in a large power system
Author :
Ghezelayagh, M. ; Gosbell, V.
Author_Institution :
Power & Water Authority, Darwin, Australia
Volume :
1
fYear :
2000
fDate :
30 Oct.-1 Nov. 2000
Firstpage :
96
Abstract :
In most frequency response type programs, it is common to assume that all harmonic sources have the same phase angle. In this paper, this assumption is investigated for distorting loads with diode rectifier front ends. Based on these investigations, equivalent models of distorting loads are proposed firstly on one distribution feeder and secondly for distribution feeders in subsystems of a large network. For the purpose of these investigations, a power electronic simulator with time domain solution has been used.
Keywords :
AC-DC power convertors; distribution networks; frequency response; harmonic analysis; harmonic distortion; load (electric); power conversion harmonics; power system analysis computing; rectifying circuits; time-domain analysis; computer simulation; diode rectifier; distorting loads; distribution feeders; equivalent models; frequency response; harmonic modeling; harmonic sources; phase angle; power electronic simulator; power system; time domain solution;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Advances in Power System Control, Operation and Management, 2000. APSCOM-00. 2000 International Conference on
Print_ISBN :
0-85296-791-8
Type :
conf
DOI :
10.1049/cp:20000371